LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE

Place of Origin China
Brand Name Kreat Power
Certification CE
Model Number KE004-06M180KE
Minimum Order Quantity 100pcs
Price Negotiation
Packaging Details Packed in bubble bags firstly, amd then reinforced with carton for outer packing
Delivery Time within 5 working days for sample and small order; within 3-4 weeks for bulk order
Payment Terms T/T, Western Union
Supply Ability 10,000pcs per Month

Contact me for free samples and coupons.

Whatsapp:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Emergency Power 6W Emergency Time 3 Hours
Load Output Voltage 20-60VDC Battery Li-ion:11.1V 2500mAh
Highlight

led emergency converter

,

dimmable led driver

,

Li ion Battery LED Emergency Driver

Leave a Message
Product Description

LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE

 

 

About Merrytek

 

Merrytek, founded in 2011, focuses on products for the lighting control industry.

 

We design and manufacture innovative microwave motion sensors, integrated sensor LED drivers and 1-10V & DALI dimmable LED drivers for lighting & electrical manufacturers, distributors, wholesalers, retrofit projects, professional lighting chain stores etc..

 

With the effort of over 30 R&D members and ISO9001:2008 qualified production lines, Merrytek supplies over 100 models with an output volume of over 200k per month for numerous applications.


1. Features
 
--Constant power output LED emergency power supply, 6W emergency power, and a wide output voltage range.
 
--With multiple protection functions: battery overcharge, over discharge protection, output short circuit protection.
 

 

2. Parameters

 

 

Charge Part Rated input voltage 220-240Vac 50Hz /60Hz
Rated input current 0.06A Max.@230Vac
Battery charging current 200mA
Battery charging time 24 hours
Emergency Part Operating mode Emergency
Load type LED
Emergency power 6W
Emergency time 3 hours
Load output voltage 20-60VDC
Battery Type Li-ion:11.1V 2500mAh
Exception Driver Requirements Input current N/A
Output current 1A MAX
LED Indication Charging The green light turns on
Fault The green light switches off
Emergency Function Test Manual test Yes
Abnormal protection Battery over-charge/deep discharge protection Yes
Output overload protection Yes
Output short circuit protection Yes

Operating

Environment

Operating temperature/humidity 0℃~65℃
Storage temperature/humidity -5℃~35℃ humidity:20%-60%(without condensation)
Case Max. Temp(Tc) 75℃
Withstand voltage 3750Vac 5mA 60S(Input “L N” – output “SEC+ SEC-)

Safety

 

& EMC

 

Electromagnetic Compatibility EN55015, EN61547,EN61000
EMC standard EN61347-2-7, EN61347-2-13
Certification requirements CE, RoHS
IP rating IP20
Others Type of protection Class 2
Input/output(terminal/wiring) specification Press terminal, wire diameter:0.5-0.75mm2
Installation type Built-in installation
Installation dimension 146*30*22.5mm
Packaging requirement White box+Instruction manual+clapboard+outer carton(K=A)
Weight 68.8g(driver),161g(battery)
Lifespan Emergency driver 30000h @Ta full load(driver not included)

Notes:

All parameters are tested on the input voltage 230Vac,environment temperature 25℃,unless otherwise specified.

 

 

 

 

 
3. Dimension (Unit:mm)

LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE 0

 

 

4. Wiring Diagram

 

LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE 1


5. Wire Preparation
 
LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE 2
 
1)Solid or Stranded wire type 0.5 - 0.75mm2
2)To make or release the wire from the terminal, use a screwdriver to push down the button.

 

6. Battery type / size

 

LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE 3

 

LED Emergency Driver Power 6W Emergency Time 3h & External Li-ion Battery KE004-06M180KE 4
 

7. Manual Test & Operation Instructions

1) Connect the wire according to wiring diagram.

2) L,N power on, Switch on S1. then the load lamp turns on,The emergency driver indicator light will turns green, emergency power supply normal charging. Turn off Switch S1, the load lamp turns off.

3) Emergency Simulation: Switch on,the load lamp turns on, press the switch(TEST SWITCH), then switch to emergency mode, the indicator light of emergency driver will be extinguished. Release the switch(TEST SWITCH), then lamp is powered by led driver, the indicator light will turn on.

4) Power off and power on, the phenomenon should be similar to emergency simulation.